AOELEC AUR1 10kA RCD (RCCB) 63A 2 Pole 1P+N (AUR1 63A)
$59.99
Price Match*
Price Match*
A 63 A two-pole (1P+N) residual current circuit breaker without overcurrent protection, rated 10 kA. It provides earth-leakage protection and isolation for final circuits. Residual current device for earth-leakage protection and isolation; High short-circuit withstand (10 kA); Fire-retardant housing material for high-temperature resistance.
AOELEC AUR1 10kA RCD (RCCB) 63A 2 Pole 1P+N (AUR1 63A): Genuine Trade Supply
You are viewing the AOELEC AUR1 10kA RCD (RCCB) 63A 2 Pole 1P+N (AUR1 63A) (SKU: AUR1 63A). This is a 100 percent genuine Circuit Protection product from our Circuit Protection range, chosen for New Zealand homes, trades and commercial projects, and backed by NZ Depot support.
Product Details: AUR1 63A
AOELEC AUR1 10kA RCD (RCCB) 63A 2 Pole 1P+N (AUR1: A 63 A two-pole (1P+N) residual current circuit breaker without overcurrent protection, rated 10 kA. It provides earth-leakage protection and isolation for final circuits.
Key Features
- ✓ Residual current device for earth-leakage protection and isolation
- ✓ High short-circuit withstand (10 kA)
- ✓ Fire-retardant housing material for high-temperature resistance
- ✓ Electronic residual-current sensing combined with electromagnetic tripping
- ✓ High level of personal safety protection
AOELEC AUR1 10kA RCD (RCCB) 63A 2 Pole 1P+N (AUR1: Specifications
| Brand | AOELEC |
| Product Code | AUR1 63A |
| Current Rating | 63A |
| Series | AUR1 10kA RCCB (Remarkable H range) |
| Rated current (In) | 63 A |
| Number of poles | 1P+N (2 pole) |
| Rated voltage (Ue) | 240 V AC |
| Rated conditional short-circuit current (Inc = IΔc) | 10 kA |
| Residual making/breaking capacity (IΔm) | 1000 A |
| Max. back-up fuse | 63 A gG/gL |
| Rated frequency | 50/60 Hz |
| IP rating | IP20 |
| Electrical endurance | 2000 cycles |
| Mechanical endurance | 10000 cycles |
| Rated impulse withstand voltage (Uimp) | 4 kV |
| Cable termination | up to 35 mm² |
| Terminal torque | 2.5 N·m |
| Terminal type | Pillar |
Installation: fixed electrical wiring in New Zealand must be installed by a licensed electrician.
Need a trade quantity or advice? Contact NZ Depot or browse more electrical supplies at NZ Depot.
Pro Tip: Ensure this AUR1 63A matches your installation. Sourced through official New Zealand supply channels for full compatibility and manufacturer warranty.
Downloads and Documents
Browse the full range of Electrical available for NZ-wide trade and retail supply.
© 2026 NZ Depot Limited. All Rights Reserved. | 100% NZ Owned and Operated. | Your Electrical Supply Specialists.
Additional information
| Weight | 0.5 kg |
|---|---|
| MPN | |
| Brand | |
| Copper Pipe (mm) | |
| Series | |
| Unit Type |
Only logged in customers who have purchased this product may leave a review.


Reviews
There are no reviews yet